NFPA 241, Standard for Safeguarding Construction, Alteration, and Demolition Operations, is not new to North Carolina. The current North Carolina Fire Code references the 2013 edition, and compliance has been required on construction projects across the state for years.
The 2024 North Carolina Building and Fire Codes have been approved but are not yet in effect, and they apply only when a project team is is approved to use them as an alternative design method. Teams that take advantage of the 2024 codes should be prepared for significantly greater compliance expectations during construction. These include a Site Safety Plan approved before work begins, a designated site safety director responsible for daily fire safety inspections, and, for large wood buildings, a Fire Exposure Analysis. For more on the broader code changes, see our related post, 2024 North Carolina Building Code Adoption.
Why These Requirements Matter
Because the 2024 North Carolina codes are based on the 2021 International codes, they would normally have referenced the 2019 edition of NFPA 241. Following the May 2023 fire at a large wood-frame apartment building under construction in Charlotte’s SouthPark area, which took the lives of two construction workers, North Carolina moved to reference the 2022 edition instead. The 2022 edition adds requirements that earlier editions lacked, including specific provisions for large wood-frame and tall mass timber construction.
Buildings are often most vulnerable to fire while under construction, before permanent fire protection systems are in place. Whichever code edition governs a project, the practices these requirements describe are worth putting in place.
Site Safety Plan
The 2024 North Carolina Fire Code introduces requirements for owners to establish a Site Safety Plan for construction, alteration, repair, and demolition work. The plan must be submitted and approved before construction begins. It must address site access, temporary fire protection, hot work, combustible materials, emergency procedures, means of egress, and fire protection system impairments.
Developing the plan during project planning is best practice. It builds fire prevention into the construction sequence and site logistics from the start, so protections are in place when they are needed rather than added after a problem appears. It also reduces corrective work, inspection issues, and the schedule delays that come with them.
Site Safety Director Responsibilities
NFPA 241 has long called for a designated person responsible for the fire prevention program. The 2024 North Carolina Fire Code defines that role more clearly. As part of the Site Safety Plan (called the Fire Prevention Program in NFPA 241), the owner must designate a site safety director (or fire prevention program manager) to carry out and enforce the plan. This person is the central point of coordination among the owner, contractor, subcontractors, design team, and AHJ. They are also responsible for daily fire safety inspections, which confirm that items such as standpipes, egress paths, fire department access, and hot work controls are in place as conditions change.
Defining this role early makes clear who is accountable for construction-phase fire safety and supports consistent implementation throughout the project.
Fire Exposure Analysis for Large Wood Buildings
Large wood-frame and tall mass timber buildings carry higher fire risk during construction because combustible structural materials are often exposed before permanent fire protection systems are operational. Through its reference to the 2022 edition of NFPA 241, the 2024 North Carolina Fire Code brings in specific requirements for these buildings (Chapters 12 and 13) that were not included in the 2013 edition, including a Fire Exposure Analysis.
Under NFPA 241, a large wood-frame structure is a wood structure that meets one of the following criteria:
- Up to three stories and greater than 150,000 square feet (13,935 m²) of aggregate total floor area; or
- More than three stories, or more than 40 feet (12.2 m) above the lowest level of fire department vehicular access, and greater than 50,000 square feet (4,645.2 m²) of aggregate total floor area.
The Fire Exposure Analysis evaluates whether passive and active fire protection features, combined with separation from adjacent structures, are adequate to allow safe egress and prevent fire spread. It is submitted with the permit documents and must be acceptable to the AHJ. The analysis often identifies mitigation measures that affect sequencing, schedule, and cost. Identifying them early lets teams build them into the construction plan rather than react to them later. For more detail, see our post, NFPA 241 – Fire Exposure Analysis.
How Code Red Consultants Can Help
Code Red Consultants works with owners, contractors, design teams, and AHJs to help project teams understand construction-phase fire safety requirements, evaluate project-specific risks, and develop practical strategies that support permitting and construction. That includes helping teams weigh whether electing to use the 2024 codes makes sense for their project. Our services include developing, or peer reviewing where required by the AHJ, the following deliverables:
- Site Safety Plans and NFPA 241 Fire Prevention Programs
- Fire Exposure Analyses
- Fire protection system impairment plans
With integrated code consulting, fire engineering, design, and field experience, we help project teams maintain a coordinated fire safety strategy from early planning through project closeout.